1220 Does not work

master
Oleg 7 months ago
parent a1981564a3
commit 59a24e06fe

@ -189,39 +189,39 @@ void FRAMDATABASE::register_configuration_parameters(SYSCTRL::SystemControlConfi
add_float( 0, &sys_config->phase_alert_monitor.voltage_decrease_level_3.period, 2.0); add_float( 0, &sys_config->phase_alert_monitor.voltage_decrease_level_3.period, 2.0);
// //
// current overload level 1 120% 60s // current overload level 1 120% 60s
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_1.level, 30.0 * 14.4); add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_1.level, 250 * 1.1);
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_1.period, 60.0); add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_1.period, 60.0);
// //
// current overload level 2 130% 10s // current overload level 2 130% 10s
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_2.level, 30.0 * 15.6);//30.0*15.6 add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_2.level, 250 * 1.2);
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_2.period, 10.0); add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_2.period, 10.0);
// //
// current overload level 3 150% 1ms // current overload level 3 150% 1ms
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_3.level, 30.0 * 18.0); add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_3.level, 250 * 1.3);
add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_3.period, 0.004); add_float( 0, &sys_config->phase_alert_monitor.current_overload_level_3.period, 0.004);
// //
// current invertor overload level 1 110% 60s // current invertor overload level 1 110% 60s
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_1.level, 13.2); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_1.level, 79 * 1.1);
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_1.period, 60.0); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_1.period, 60.0);
// //
// current invertor overload level 2 130% 10s // current invertor overload level 2 130% 10s
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_2.level, 15.6); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_2.level, 79 * 1.2);
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_2.period, 10.0); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_2.period, 10.0);
// //
// current invertor overload level 3 150% 1ms // current invertor overload level 3 150% 1ms
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_3.level, 18.0); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_3.level, 79 * 3.2);
add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_3.period, 0.004); add_float( 0, &sys_config->phase_alert_monitor.current_invertor_overload_level_3.period, 0.004);
// //
// current input overload level 1 110% 60s // current input overload level 1 110% 60s
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_1.level, 99.0); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_1.level, 131.0 * 1.1);
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_1.period, 60.0); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_1.period, 60.0);
// //
// current input overload level 2 130% 10s // current input overload level 2 130% 10s
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_2.level, 117.0); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_2.level, 131.0 * 1.2);
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_2.period, 10.0); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_2.period, 10.0);
// //
// current input overload level 3 150% 1ms // current input overload level 3 150% 1ms
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_3.level, 135.0); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_3.level, 131.0 * 1.3);
add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_3.period, 0.004); add_float( 0, &sys_config->phase_alert_monitor.current_input_overload_level_3.period, 0.004);
//<> //<>

@ -318,17 +318,18 @@ void PhaseAlertMonitor::_execute_operational(float urmsa, float urmsb, float urm
m_voltage_bc_exceed_level_4.execute(urmsb); m_voltage_bc_exceed_level_4.execute(urmsb);
m_voltage_ca_exceed_level_4.execute(urmsc); m_voltage_ca_exceed_level_4.execute(urmsc);
/* /*
m_voltage_a_decrease_level_1.execute(urmsa); m_voltage_ab_decrease_level_1.execute(urmsa);
m_voltage_b_decrease_level_1.execute(urmsb); m_voltage_bc_decrease_level_1.execute(urmsb);
m_voltage_c_decrease_level_1.execute(urmsc); m_voltage_ca_decrease_level_1.execute(urmsc);
m_voltage_a_decrease_level_2.execute(urmsa); m_voltage_ab_decrease_level_2.execute(urmsa);
m_voltage_b_decrease_level_2.execute(urmsb); m_voltage_bc_decrease_level_2.execute(urmsb);
m_voltage_c_decrease_level_2.execute(urmsc); m_voltage_ca_decrease_level_2.execute(urmsc);
*/
m_voltage_a_decrease_level_3.execute(urmsa); /*
m_voltage_b_decrease_level_3.execute(urmsb); m_voltage_ab_decrease_level_3.execute(urmsa);
m_voltage_c_decrease_level_3.execute(urmsc); m_voltage_bc_decrease_level_3.execute(urmsb);
m_voltage_ca_decrease_level_3.execute(urmsc);
*/ */
m_current_a_overload_level_1.execute(irmsa); m_current_a_overload_level_1.execute(irmsa);
m_current_b_overload_level_1.execute(irmsb); m_current_b_overload_level_1.execute(irmsb);

@ -53,10 +53,10 @@ namespace SYSCTRL
#if TYPECONTROL == DIRECTREVERSECONTROL #if TYPECONTROL == DIRECTREVERSECONTROL
#define HEADER_CLASS_ID ((int16_t)(0x0010)) #define HEADER_CLASS_ID ((int16_t)(0x0FB0))
#define HEADER_PART_ID ((int16_t)(0x0010)) #define HEADER_PART_ID ((int16_t)(0x0FB0))
#define HEADER_SOFTWARE_VERSION ((int16_t)(0x0010)) #define HEADER_SOFTWARE_VERSION ((int16_t)(0x0FB0))
#define FOOTER_FOOT ((int16_t)(0x0010)) #define FOOTER_FOOT ((int16_t)(0x0FB0))
#endif #endif

@ -596,7 +596,7 @@ void SystemControl::_execute_operational()
m_environment.system_faults_register.equipment.signal.km1 = m_km1_control_fault.status.signal.fault; m_environment.system_faults_register.equipment.signal.km1 = m_km1_control_fault.status.signal.fault;
m_environment.system_faults_register.equipment.signal.km2 = m_km2_control_fault.status.signal.fault; m_environment.system_faults_register.equipment.signal.km2 = m_km2_control_fault.status.signal.fault;
m_environment.system_faults_register.equipment.signal.km3 = m_km3_control_fault.status.signal.fault; m_environment.system_faults_register.equipment.signal.km3 = m_km3_control_fault.status.signal.fault;
//m_environment.system_faults_register.equipment.signal.sync_to_grid = !m_pll_abc_input_voltage.get_sync() & m_environment.input_discrete.signal.auxiliary_q1; m_environment.system_faults_register.equipment.signal.sync_to_grid = !m_pll_abc_input_voltage.get_sync() & m_environment.input_discrete.signal.auxiliary_q1;
} }

@ -138,7 +138,7 @@ union BoolRegister
#define CURRENT_LIMIT_RMS (float)(100.0) #define CURRENT_LIMIT_RMS (float)(100.0)
#define CURRENT_PFC_RMS (float)(0.0) #define CURRENT_PFC_RMS (float)(0.0)
#define GRID_VOLTAGE_REFERENCE (float)(6000.0) #define GRID_VOLTAGE_REFERENCE (float)(5700.0) //6000
#define GRID_VOLTAGE_HIGH_LIMIT (float)(6600.0) #define GRID_VOLTAGE_HIGH_LIMIT (float)(6600.0)
#define CELL_DC_VOLTAGE_REFERENCE (float)(5.0*950.0) #define CELL_DC_VOLTAGE_REFERENCE (float)(5.0*950.0)
@ -285,13 +285,13 @@ union BoolRegister
#define NOMINAL_GRID_VOLTAGE (float)6000.0 #define NOMINAL_GRID_VOLTAGE (float)6000.0
#define PROTECTION_EXCEED_VOLTAGE_LEVEL_1_PERCENT (float)10.0 #define PROTECTION_EXCEED_VOLTAGE_LEVEL_1_PERCENT (float)35.0 // 10.0 was changed to 35.0
#define PROTECTION_EXCEED_VOLTAGE_LEVEL_2_PERCENT (float)15.0 #define PROTECTION_EXCEED_VOLTAGE_LEVEL_2_PERCENT (float)35.0 // 15.0 was changed to 35.0
#define PROTECTION_EXCEED_VOLTAGE_LEVEL_3_PERCENT (float)20.0 #define PROTECTION_EXCEED_VOLTAGE_LEVEL_3_PERCENT (float)35.0 // 25.0 was changed to 35.0
#define PROTECTION_EXCEED_VOLTAGE_LEVEL_4_PERCENT (float)50.0 #define PROTECTION_EXCEED_VOLTAGE_LEVEL_4_PERCENT (float)20.0 // 50.0 was changed to 20.0
#define PROTECTION_DECREASE_VOLTAGE_LEVEL_1_PERCENT (float)15.0 #define PROTECTION_DECREASE_VOLTAGE_LEVEL_1_PERCENT (float)15.0
#define PROTECTION_DECREASE_VOLTAGE_LEVEL_2_PERCENT (float)25.0 #define PROTECTION_DECREASE_VOLTAGE_LEVEL_2_PERCENT (float)25.0
#define PROTECTION_DECREASE_VOLTAGE_LEVEL_3_PERCENT (float)35.0 #define PROTECTION_DECREASE_VOLTAGE_LEVEL_3_PERCENT (float)40.0 // 35.0 was changed to 40.0

Loading…